WIRED TO COMPLY: UNDERSTANDING THE STANDARD TEST REPORT – PART 7

Written by: Grant Seeman – National Technical Advisor

A practical series on the four inspection questions and 15 tests in SANS 10142-1

Part 7: Test 3 – Continuity of ring circuits

The third test in Section 4 of the standard test report reads:

“Continuity of ring circuits (if applicable).”

This test applies only where ring circuits form part of the electrical installation.

A ring circuit starts at a distribution board, supplies the connected points and returns to the same distribution board, completing the ring.

Unlike a conventional radial circuit, which is supplied from one end, a ring circuit provides two paths through which current can flow to the connected loads.

Kirchhoff’s current law tells us that current entering a junction must equal the current leaving it. In a ring circuit, load current divides between the two paths according to their impedance. Equal paths may share current equally, but a load nearer one end will generally draw more current through the lower-impedance path.

A branch, or spur, teed off a ring does not form part of the continuous ring. It has only one supply path and must be treated as a radial portion of the circuit, with suitably sized conductors and appropriate overcurrent protection.

Clause 6.2.1.2 permits spurs with conductors of reduced current-carrying capacity, provided the applicable overcurrent-protection requirements are satisfied.

Why is this important?

The safety of a ring circuit depends on its conductors being correctly connected and the ring remaining complete.

A break may force the load current through only one side of the ring, effectively creating a radial circuit. Depending on the loading, that remaining path could carry excessive current and overheat.

A break in one of the ring conductors may go unnoticed because the connected points can continue receiving electricity, even though the ring itself is no longer electrically complete.

What must be confirmed?

The registered person must establish that:

  • Ring circuits, where installed, are correctly identified.
  • Each phase and neutral conductor forming the ring has continuity between its two ends.
  • Both ends of the relevant conductors are correctly terminated at the distribution board.
  • Any branches teed off from the ring are recognised as radial portions and are correctly sized and protected.
  • Each socket-outlet connected to a ring circuit is correctly marked.

Clause 6.6.1.12 requires both ends of the live and neutral conductors of a ring circuit to be crimped together. It also requires ring circuits to be clearly and permanently identified by a notice or tag.

Clause 6.15.8 requires each socket-outlet connected to a ring circuit to be marked accordingly.

How is the test carried out?

Start at the distribution board and identify any ring circuits connected to it.

Before disconnecting conductors for testing, the circuit must be safely isolated and proven dead. Particular care is required where alternative supplies may be present.

Clause 8.6.4 requires both ends of each live conductor to be disconnected and separated so that the continuity of the circuit can be tested.

Using a suitable continuity-testing instrument, measure between the two ends of the conductor to establish whether an uninterrupted electrical path exists.

The phase and neutral conductors must be checked individually. Separating their ends helps prevent other connected paths from giving a misleading result.

If there is no continuity, the conductor may be broken, disconnected or incorrectly terminated somewhere along the circuit.

The continuity and other applicable safety requirements of any radial branches must be checked separately; proving the ring is complete does not prove that its spurs comply.

After testing, reconnect the conductors correctly. Clause 8.6.4 requires the two ends of each live conductor to return to the same terminal, while Clause 6.6.1.12 requires the ends of the live and neutral conductors to be crimped together.

Test 3 does not call for a numerical resistance value on the standard test report. Confirm the continuity result where a ring is installed; if no ring circuits exist, the test is not applicable.

Common mistakes

Common mistakes include:

  • Assuming that a ring circuit is continuous simply because the socket-outlets are working.
  • Testing the circuit without separating the conductor ends.
  • Testing only the phase conductor and overlooking the neutral.
  • Reconnecting the two ends incorrectly after testing.
  • Failing to crimp the conductor ends together as required.
  • Treating a branch teed off from a ring as though it also has two current paths.
  • Failing to check that the conductors and overcurrent protection of radial branches are suitable.
  • Not identifying ring circuits at the distribution board or marking the connected socket-outlets.

What if the result is unacceptable?

Where continuity cannot be established, the ring circuit must be investigated.

The fault might be caused by a loose terminal, a disconnected conductor, an incorrect joint or a conductor that has been damaged during previous alterations.

The fault must be located and corrected, and the circuit must then be retested.

Clause 8.6.1 requires a failed test to be repeated after the fault has been corrected. Other tests affected by the fault must also be repeated.

Regulation 9(3) of the Electrical Installation Regulations requires the registered person to refuse to issue the Certificate of Compliance until the fault or defect has been rectified.

Practical tip

Do not ask only:

“Are all the socket-outlets working?”

Ask:

“Have I proved that each conductor forms a complete ring, that both ends are correctly connected at the distribution board, and that any branches are correctly treated as radial portions of the circuit?”

Key takeaway

A ring circuit may continue supplying electricity even when one of its conductors is broken. The continuity test confirms that both paths are complete, rather than relying on the fact that equipment still works.

Where ring circuits are installed, their continuity must be confirmed by testing. Where no ring circuits exist, the test is not applicable.

Where this information comes from

This article is based on SANS 10142-1:2026 Edition 3.3, particularly Clauses 6.2.1.1, 6.2.1.2, 6.2.1.3, 6.6.1.12, 6.15.8, 8.6.1 and 8.6.4, together with Section 4 of the standard test report. The explanation of current distribution is based on Kirchhoff’s circuit laws. The requirement relating to rectification of defects before certification is taken from Regulation 9(3) of the Electrical Installation Regulations, 2009.